Beckhoff KL1501 User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 19
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
Product Overview
KL1501 3
2 Product Overview
2.1 Technical data
Product name KL1501
Number of counters
1 or 2
Rated load voltage
24 V
DC
(20 V ... 29 V)
‘0’ signal voltage
-3 V ... 5 V
‘1’ signal voltage
15 V ... 30 V
Switching frequency
100 kHz (2 kHz by switching U/D)
Input current
typical 5 mA.
Current consumption from K-Bus
typical 50 mA
Counter depth
32 bit or 2 x 16 bit
Electrical isolation
500 Vrms (K-Bus / field voltage)
Bit width in the process image
40 I/O: 32 bits data, 8 bits control/status
Configuration
no address settings, configurations via bus coupler or control system
Weight approx.
50 g
Operating temperature
C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration / Shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC resistance burst / ESD
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
any
Type of protection
IP20