Mounting and cabling
CU2608 13
Power cable conductor losses
The ZK2020-xxxx-yyyy power cables should not exceed the total length of 15 m at 4 A (with continuation). When
planning the cabling, note that at 24 V nominal voltage, the functionality of the module can no longer be assured if the
voltage drop reaches 6 V. Variations in the output voltage from the power supply unit must also be taken into
account.
Example
8 m power cable with 0.34 mm² cross-section has a voltage drop of 3.2 V at 4 A.