Beckhoff BK3000 User Manual Page 30

  • Download
  • Add to my manuals
  • Print
  • Page
    / 67
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 29
PROFIBUS coupler BK3xx0 in the PROFIBUS DP
30 BK3xxx/LC3100
BK3500
02
01
+
+
PE
PE
RUN
BF
DIA
PROFIBUS
BECKHOFF
24V
0V
00
X0
BK3500
Field Bus
Signal Input
Field Bus
Signal Output
Configuration
Interface
Address
Selector
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
Baud
rate
x1
x10
1
O
N
2
Profibus fiber optic net
Characteristics
Characteristics
Topologiy
Subring
max. amount of
stations
93,75 kBaud: 13 187,5 kBaud: 12
500 kBaud: 12 1500 kBaud : 10
min./max.length
between two
stations
Coordinator – Station: Lmin = 1 m, Lmax = 34 m
Station – Station: Lmin = 1 m, Lmax = 25 m
Station – Coordinator: Lmin = 0 m, Lmax = 46 m
Bus connector
2 x HP Simplex connector (included)
APF (plastic)- fiber conductor (Z1101)
Baud rate
93,75; 187,5; 500; 1500 kBaud
Switch position
S1=0,S2=0; S1=0,S2=1; S1=1,S2=0; S1=1,S2=1
RS485
Fundamental
characteristics
RS-485
Data transfer
technology to the
Profibus standard
Network topology
Linear bus, active bus terminator at both ends, branch
lines are possible
Medium
Shielded twisted cable, shielding may be dispensed with in
suitable environments (electromagnetic compatibility)
Number of stations
32 stations in each segment without repeaters, extendible
to 127 with repeaters
Max. bus length
without repeaters
100 m at 12 Mbit/s
200 m at 1500 Kbit/s, up to 1.2 km at 93.75 Kbit/s
with repeaters
Using repeaters (line amplifiers) increases the max. bus
length to the order of 10 km. The number of possible
repeaters is at least 3 and may be up to 10, depending on
the manufacturer
Transfer rates
9.6, 19.2, 93.75, 187.5, 500, 1500 Kbit/s, up to 12 Mbit/s in
discrete steps
Plug
9-Pin D-Sub plug
Page view 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 66 67