Beckhoff CX1000 User Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
Product Overview
Embedded PC 23
RS485 without Echo, Drop-Point ( without Termination)
DIP Status Function
1 off Echo on
2 on Echo off
3 on Auto send on
4 off Always send on
5 off Auto receive on
6 on Always receive on
7 off Term on
8 off Term on
RS485 with Echo, Drop-Point ( without Termination)
DIP Status Function
1 on Echo on
2 off Echo off
3 on Auto send on
4 off Always send on
5 off Auto receive on
6 on Always receive on
7 off Term on
8 off Term on
Settings DIP Switches RS422:
RS422 full duplex end point
DIP Status Function
1 on Echo on
2 off Echo off
3 off Auto send on
4 on Always send on
5 off Auto receive on
6 on Always receive on
7 on Term on
8 on Term on
The dip switches for the configuration of the RS485/422 interfaces can be found at the left side of the module. If you
remove the grey cover you can see the switch.
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 49 50

Comments to this Manuals

No comments