Commissioning
Fig.157: Entering the position
5.4.6 Velocity sensorless
In Velocity sensorless mode, the EL70x7 operates in the cyclic velocity interface. A defined velocity can be
set via the STM Velocity variable.
Prerequisites
• This mode can be used with a connected encoder or with the internal counter (without encoder).
• The process data can be transferred with TwinCAT NC or directly from the PLC.
Step by Step
• Add the terminal to the configuration as described in the section TwinCAT configuration settings –
manual [}66] or – Online scan [}72].
• Link the terminal with the NC as described in section Integration into the NC configuration [}104] (if
TwinCAT NC is used).
• Configure the EL70x7
◦ automatically - import the XML motor file into the startup directory as described in section Set-
tings in the CoE - automatic [}105].
◦ manually - configure the parameters as described in section Settings in the CoE - manual
[}105].
• Set the operating mode in the CoE directory to Velocity sensorless, Fig. "Velocity sensorless mode".
EL70x7 137Version 1.0