Beckhoff EL7037 User Manual Page 177

  • Download
  • Add to my manuals
  • Print
  • Page
    / 227
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 176
Configuration by means of the TwinCAT System Manager
Index 1C33 SM input parameter (part 1)
Index Name Meaning Data type Flags Default value
1C33:0 SM input parame-
ter
Synchronization parameters for the inputs UINT8 RO 0x20 (32
dec
)
1C33:01 Sync mode Current synchronization mode:
0: Free Run
1: Synchronous with SM 3 event (no outputs
available)
2: DC - Synchronous with SYNC0 Event
3: DC - Synchronous with SYNC1 Event
34: Synchronous with SM 2 event (outputs
available)
UINT16 RW 0x0022 (34
dec
)
1C33:02 Cycle time
as 1C32:02 [}176]
UINT32 RW 0x000F4240
(1000000
dec
)
1C33:03 Shift time Time between SYNC0 event and reading of the inputs (in
ns, only DC mode)
UINT32 RO 0x00000000 (0
dec
)
1C33:04 Sync modes sup-
ported
Supported synchronization modes:
Bit 0: free run is supported
Bit 1: synchronous with SM 2 event is supported
(outputs available)
Bit 1: synchronous with SM 3 event is supported
(no outputs available)
Bit 2-3 = 01: DC mode is supported
Bit 4-5 = 01: input shift through local event
(outputs available)
Bit 4-5 = 10: input shift with SYNC1 event (no
outputs available)
Bit 14 = 1: dynamic times (measurement through
writing of 1C32:08 [}176] or 1C33:08 [}177])
UINT16 RO 0x0C07 (3079
dec
)
1C33:05 Minimum cycle
time
as 1C32:05 [}176]
UINT32 RO 0x0003D090
(250000
dec
)
1C33:06 Calc and copy
time
Time between reading of the inputs and availability of the
inputs for the master (in ns, only DC mode)
UINT32 RO 0x00000000 (0
dec
)
1C33:07 Minimum delay
time
UINT32 RO 0x00000000 (0
dec
)
Index 1C33 SM input parameter (part 2)
Index Name Meaning Data type Flags Default value
1C33:08 Command
as 1C32:08 [}176]
UINT16 RW 0x0000 (0
dec
)
1C33:09 Maximum delay
time
Time between SYNC1 event and reading of the inputs (in
ns, only DC mode)
UINT32 RO 0x00000000 (0
dec
)
1C33:0B SM event missed
counter
as 1C32:11 [}176]
UINT16 RO 0x0000 (0
dec
)
1C33:0C Cycle exceeded
counter
as 1C32:12 [}176]
UINT16 RO 0x0000 (0
dec
)
1C33:0D Shift too short
counter
as 1C32:13 [}176]
UINT16 RO 0x0000 (0
dec
)
1C33:14 Frame repeat time UINT32 RW 0x00000000 (0
dec
)
1C33:20 Sync error
as 1C32:32 [}176]
BOOLEAN RO 0x00 (0
dec
)
Index F000 Modular device profile
Index Name Meaning Data type Flags Default value
F000:0 Modular device
profile
General information for the modular device profile UINT8 RO 0x02 (2
dec
)
F000:01 Module index dis-
tance
Index spacing of the objects of the individual channels UINT16 RO 0x0010 (16
dec
)
F000:02 Maximum number
of modules
Number of channels UINT16 RO 0x0003 (3
dec
)
EL70x7 177Version 1.0