Comissioning/Configuration
Index Name Meaning Datatype Flags Default
8011:0 DIGSafestate
value
UINT8 RO 0x08(8
dec
)
8011:01 Output9 0
bin
DIGSafestate
valuefor
output9=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output9=1
8011:02 Output10 0
bin
DIGSafestate
valuefor
output10=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output10=1
8011:03 Output11 0
bin
DIGSafestate
valuefor
output11=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output11=1
8011:04 Output12 0
bin
DIGSafestate
valuefor
output12=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output12=1
8011:05 Output13 0
bin
DIGSafestate
valuefor
output13=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output13=1
8011:06 Output14 0
bin
DIGSafestate
valuefor
output14=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output14=1
8011:07 Output15 0
bin
DIGSafestate
valuefor
output15=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output15=1
8011:08 Output16 0
bin
DIGSafestate
valuefor
output16=0
BOOLEAN RW 0
bin
1
bin
DIGSafestate
valuefor
output16=1
Index8020DIGSafestateactiveCh.3
TheoutputsthebitDIGSafestateactiveissetfor,areswitchedtothevaluethatisspecifiedinSafestate
value,incaseofstatusOperational(OP)isleft.
StatusOperational(OP)isleftifcommunicationtothemasterisinterrupted,forexampleatpower
breakdownatthemasterorcablebreakage.
EP2xxx 165Version2.1.0