Productoverview
Attention
Forswitchoffintheeventofafault,donoexternalsensorpowersupply
IfthedesignofyourinstallationissuchthatthepowersupplyvoltageUpisswitchedoffin
theeventofafault,youmustnotpowertheconnectedsensorsexternally,butonlythrough
theEP23390021!Otherwise,whentheUpenergyisswitchedoff,theEP23390021can
continuetodrawenergyfromtheexternalsensorpowersupply,andtheoutputswillnotbe
switchedoff!
Quicklinks
Installation
2.9.2 EP23390022Introduction
Fig.27:EP23390022
16digitalinoroutputs,24V
DC
TheEP23390022EtherCATBoxhas16digitalchannels,eachofwhichcanoptionallybeoperatedasan
inputorasanoutput.Aconfigurationifachannelshouldbeusedasinputorasanoutputisnotnecessary;
theinputcircuitisinternallyconnectedtotheoutputdriver,soasetoutputisdisplayedautomaticallytothe
inputprocessimage.
Theoutputshandleloadcurrentsofupto0.5A,areshortcircuitproofandprotectedagainstinversepolarity.
Thefilterconstantoftheinputsis3ms.
Thestateofeachsignalisindicatedbymeansoflightemittingdiodes.ThesignalsareconnectedviaM12
connectors.
EP2xxx 41Version2.1.0