Productoverview
Fig.50:EP28160010,DIGOutputsDevice
Setsafestate
Setsthemoduletosafestate.
Resetoutputs
Resetsbits„ErrorchannelX“ofthemodule.Theoutputsareactivatedagain.
2.13.5 Configuration
AnumberofparameterizationscanbecarriedoutfortheEP23160003,EP23160008,28160008and
28160010modulesontheC0EOnlinetabintheTwinCATSystemManager.
ThedescriptionoftheparameterizationsisdonewiththehelpofEP23160008butissuitableforallthis
modules.
Definitionsforthebehavioroftheoutputsincaseofnetworkfailure
Withbit8000:0n(SafeStateActive)youcanspecifythatchannelnshouldadoptaspecifiedvalue(Safe
StateValue)ifthenetworkcommunicationisinterruptedornot.
Withbit8001:0n(SafeStateValue)youdefinethisspecificvalueforchanneln.
Note
SafeStateValueatnetworkstartup
ThenetworktransfersoutputprocessdataonlyatthenetworkstatesBOOTundOpera
tional(OP).AlsoatthenetworkstatesINIT,PreOperational(PREOP)andSaveOpera
tional(SAFEOP)passedtroughduringnetworkstartupnooutputprocessdataistransmit
ted.IfSafeStateisactivatedforanoutput,thisoutputadoptsthespecifiedvaluealsodur
ingnetworkstartup.
8000:0DIGSafestateactiveCh.1
Note
Observethemaximumshortcircuitcurrent!
Whendimensioningthepowersupplyunitandchoosingthefuses,observethattheshort
circuitcurrentisapproximately1.7A.