Productoverview
2.5 EP20280032
2.5.1 EP20280032Introduction
Fig.8:EP20280032
8digitaloutputs24V
DC
,I
max
2,8A(Σ16A)
TheEP20280032EtherCATBoxwithdigitaloutputsconnectsthebinarycontrolsignalsfromthecontroller
ontotheactuatorsattheprocesslevel.
Theeightoutputshandleloadcurrentsofupto2.8Aeach,althoughthetotalcurrentislimitedto16A.
Thencethismodulesareespeciallysuitableforapplications,atwhichahighutilizationfactorwithhighoutput
currentisnecessary.
Thesignalstateisindicatedbymeansoflightemittingdiodes.ThesignalsareconnectedviaM12type
connectors.Theoutputsareshortcircuitproofandprotectedagainstinverseconnection.
Pin2and4ofchannel0and1,channel2and3,channel4and5aswellaschannel6and7areconnected.
Thereforealsoactuatorswitchneeds2outputscanbeconnectedviaoneM12cable.