Mountingandcabling
InsomeoftheanalogmodulesthesensorsoractuatorsaresuppliedbyUpthismeans,forinstance,thatin
thecaseof0...10Vinputs,anyreferencevoltage(0...30V)maybeconnectedtoUp;thisisthenavailableto
thesensors(e.g.smoothed10Vformeasuringpotentiometers).
Detailsofthepowersupplymaybetakenfromthespecificmoduledescriptions.
Attention
Electricalisolationmaybecancelled!
Ifdigitalandanalogfieldbusboxesareconnecteddirectlyviafourcorepowerleads,the
analogsignalsinthefieldbusboxesmaybenolongerelectricallyisolatedfromthecontrol
voltage!
3.3.2 StatusLEDsforpowersupply
Fig.83:StatusLEDsforpowersupply
LEDdisplay
LED Display Meaning
Us(Controlvoltage) off ThepowersupplyvoltageUsisnotpresent
greenilluminated ThepowersupplyvoltageUsispresent
reedilluminated Becauseofoverload(current>0.5A)thesensorsupply
generatedfrompowersupplyvoltageUswasswitchedofffor
allsensorsfedfromthis.
Up(Auxiliaryvoltage) off ThepowersupplyvoltageUpisnotpresent
greenilluminated ThepowersupplyvoltageUpispresent
EP2xxx 89Version2.1.0